3.8 Main Circuit Wiring
68 YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
■ Three-Phase 400 V Class
Table 3.3 Wire Gauge and Torque Specifications (Three-Phase 400 V Class)
2A0169
R/L1, S/L2, T/L3 70 50 to 95
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 70 50 to 95
–, +1 – 35 to 95
+3 – 50 to 95
35 25 to 35 M8
9 to 11
(79.7 to 97.4)
2A0211
R/L1, S/L2, T/L3 95 70 to 95
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 95 70 to 95
–, +1 – 35 to 95
+3 – 50 to 95
50 25 to 50 M8
9 to 11
(79.7 to 97.4)
2A0250
R/L1, S/L2, T/L3 95 × 2P 95 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 95 × 2P 95 to 150
–, +1 – 70 to 150
+3 – 35 to 150 M10
18 to 23
(159 to 204)
95 95 to 150 M12
32 to 40
(283 to 354)
2A0312
R/L1, S/L2, T/L3 95 × 2P 95 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 95 × 2P 95 to 150
–, +1 – 70 to 150
+3 – 70 to 150 M10
18 to 23
(159 to 204)
95 95 to 150 M12
32 to 40
(283 to 354)
2A0360
R/L1, S/L2, T/L3 240 95 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 240 95 to 300
–, +1 – 125 to 300
+3 – 70 to 300 M10
18 to 23
(159 to 204)
120 120 to 240 M12
32 to 40
(283 to 354)
2A0415
R/L1, S/L2, T/L3 120 × 2P 95 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 300 95 to 300
–, +1 – 150 to 300
+3 – 70 to 300 M10
18 to 23
(159 to 204)
120 120 to 240 M12
32 to 40
(283 to 354)
Model
CIMR-A
Terminal
Recommended Gauge
mm
2
Applicable
Gauge
mm
2
Screw
Size
Tightening
Torque
Nxm (lb.in.)
4A0002
4A0004
R/L1, S/L2, T/L3 2.5 2.5 to 6
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 2.5 2.5 to 6
–, +1, +2 – 2.5 to 6
B1, B2 – 2.5 to 6
2.5 2.5 to 4
4A0005
4A0007
4A0009
R/L1, S/L2, T/L3 2.5 2.5 to 6
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 2.5 2.5 to 6
–, +1, +2 – 2.5 to 6
B1, B2 – 2.5 to 6
2.5 2.5 to 6
4A0011
R/L1, S/L2, T/L3 2.5 2.5 to 6
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 2.5 2.5 to 6
–, +1, +2 – 2.5 to 6
B1, B2 – 2.5 to 6
2.5 2.5 to 6
Model
CIMR-A
Terminal
Recommended Gauge
mm
2
Applicable
Gauge
mm
2
Screw
Size
Tightening
Torque