7.2  MECHATROLINK Communications Settings
7.2.2  MECHATROLINK Detail Definition Dialog Box Details
7-10
Link Assignment Tab Page
The Link Assignment Tab Page displays the assignment settings for all slave devices that were 
detected during self-configuration (MECHATROLINK-III-connected devices, such as SERVO-
PACKs or distributed I/O).
Refer to the following section for details on each item.
 Item Details on page 7-10
 Item Details
This section provides details on the items that are displayed on the Link Assignment Tab Page.
ST #
This is the station number.
The number of rows that is displayed corresponds to the number of slave stations that is set on 
the Transmission Parameters Tab Page.
This number is automatically assigned.
ADR
Set the station address of the slave station.
No. Item Description
ST # Displays the station number.
ADR Sets the station address of the slave station.
ExADR
Sets the individual extended addresses when multi-station modules 
(multi-slaves) are grouped together as a single node.
VENDOR Sets the vendor name of the device.
DEVICE Sets the slave model.
PROFILE Sets the profile to use.
BYTE Sets the number of transmission bytes.
INPUT Sets the first register address of the input area.
OUTPUT Sets the first register address of the output area.
D Enables or disables the I/O registers.
SIZE Sets the input or output size in words.
SCAN Sets the scan in which the input or output is performed.
Comment Enter a comment of up to 32 characters if required.
Always save all settings to the flash memory after you change them.
12
11