10.2 Setup Procedure
10.2.2 Inverter Settings
10-8
11.
Click the [+] Expand Button for Run status (IW00).
12.
Confirm that bit 3 (Inverter Ready) is 1 (ON).
If it is 1 (ON), the Inverter is ready and communications were established successfully.
If it is 0 (OFF), communications have not been established between the MP3000 and Inverter. Check
the connection of the MECHATROLINK-III communications cable and the settings on the MECHA-
TROLINK Communications Definition Tab Page.
Refer to the following section for details on the MECHATROLINK communications definitions.
7.2 MECHATROLINK Communications Settings on page 7-7
This concludes the procedure.
STEP 2: Set the Required Fixed Parameters
1.
Display the Function List Dialog Box using steps 8 and 9 in the
Manual Definition
Method procedure for STEP 1.
2.
Click the Fixed Parameter Icon.
The Fixed Parameter Tab Page will be displayed.
3.
Set the required parameters in the setting column.
This concludes the procedure.
If you manually set the Module configuration definitions for an Inverter, always save the fixed
parameters. If you do not save the fixed parameters, the current values of the setting parameters
will be restored to the default values when you restart the Inverter.