10.2 Setup Procedure
10.2.2 Inverter Settings
10
Inverter Operation
10-9
STEP 3: Confirm That the Inverter Is Ready for Operation
1.
Display the Function List Dialog Box using steps 8 and 9 in the
Manual Definition
Method procedure for STEP 1.
2.
Click the Setting Parameter Icon.
The Setting/Monitor Parameter Tab Page will be displayed.
3.
Double-click the setting column cell for Run command setting (OW00).
The Edit Dialog Box will be displayed.
4.
Set bit D (Drive Permission) of Run command setting (OW00) to 1 (ON).
5.
Click the Apply Button.
6.
In the monitor parameters on the same tab page, click the [+] Expand Button for Run
status (IW00).
7.
Confirm that bit 0 (Operation ready) is 1 (ON).
Note: If the status is 0 (OFF), confirm that a command is not being executed in the Command setting
parameter (OW08).
If the current command is Inverter Drive Control, first select another command and then set bit D
(Drive Permission) in Run command setting (OW00) to 0 (OFF) and then change it back to 1
(ON).
This concludes the procedure.