10.2 Setup Procedure
10.2.2 Inverter Settings
10-10
STEP 4: Execute the Inverter Operation Control Command
1.
Double-click the setting column cell for Command (OW08) in the setting parame-
ters.
The Edit Dialog Box will be displayed.
2.
Click the Button and select Inverter Drive Control from the list.
Note: Wait for at least one high-speed scan after you set bit D (Drive Permission) in Run command setting
(OW00) to 1 (ON) in step 4 of the STEP 3 procedure before you make this setting.
The following parameters will be enabled when you execute the Inverter Drive Control command.
Set the Output Data Option Selection (OW0C) and Input Data Option Selection (OW0D)
to enable the output data from OW13 to OW16 and the input data from IW13 to
IW1D as required.
Refer to the following section for details on the Output Data Option Selection and Input Data Option
Selection parameters.
10.2.3 I/O Options on page 10-12
This concludes the procedure.
<Inverter Output>
Input Command (OW10)
Speed Reference (OW11)
Torque Reference (OW12)
<Inverter Input>
Output Frequency (IW11)
Output Current (IW12)
M-III Inverter Command Status (IL2A)
M-III Command Status (IW2C)