10.4 Main Commands and Subcommands
10.4.3 Main Command Details
10-24
Monitor Parameters
Write User Constant
Description
Writes the specified inverter user constant to a constant in the Inverter.
Note: You must execute the User Constant RAM Writing command to enable the data written by executing the
Write User Constant command. Refer to the following section for details.
User Constant RAM Writing on page 10-26
Setting Parameters
Name Register No.
Setting
Range
Remarks
Warning IL02 Bit
Alarm IL04 Bit
Command Response Code IW08 0 to 8 02: Read User Constant
Command Status IW09 Bit
Bit 0 (Command execution
flag)
ON during execu-
tion
Bit 3 (Command error com-
pleted status)
ON when an error
occurs during
command pro-
cessing
Bit 8 (Command execution
completed)
OFF during execu-
tion, and ON when
execution is com-
pleted.
M-III Inverter Command Sta-
tus
IL2A Bit Inverter operating status
M-III Command Status IW2C Bit Inverter command processing status
Inverter Alarm Code IW32 0 to FFFFH Inverter alarm code
Inverter User Constant
Number
IW3C 0 to FFFFH
User Constant
Reading Data 1
IW3E 0 to 65535
User Constant
Reading Data 2
IW3F 0 to 65535
User Constant
Reading Data 3
IW40 0 to 65535
User Constant
Reading Data 4
IW41 0 to 65535
Name Register No. Setting Range Remarks
Command OW08 0 to 8 03: Write User Constant
Inverter User Constant Number OW3C 0 to FFFFH
Inverter User Constant Number
Size
OW3D 1 to 4
Inverter User Constant Set Point 1 OW3E 0 to 65535
Inverter User Constant Set Point 2 OW3F 0 to 65535
Inverter User Constant Set Point 3 OW40 0 to 65535
Inverter User Constant Set Point 4 OW41 0 to 65535