10.4 Main Commands and Subcommands
10.4.3 Main Command Details
10-25
Monitor Parameters
Alarm Monitor
Description
Reads the alarm that is occurring in the Inverter.
Setting Parameters
Monitor Parameters
Name Register No.
Setting
Range
Remarks
Warning IL02 Bit −
Alarm IL04 Bit −
Command Response Code IW08 0 to 8 03: Write User Constant
Command Status IW09 Bit
Bit 0 (Command execution
flag)
ON during execu-
tion
Bit 3 (Command error
completed status)
ON when an error
occurs during
command pro-
cessing
Bit 8 (Command execution
completed)
OFF during execu-
tion, and ON when
execution is com-
pleted.
M-III Inverter Command Sta-
tus
IL2A Bit Inverter operating status
M-III Command Status IW2C Bit Inverter command processing status
Inverter Alarm Code IW32 0 to FFFFH Inverter alarm code
Inverter User Constant Num-
ber
IW3C 0 to FFFFH −
Name Register No. Setting Range Remarks
Command OW08 0 to 8 04: Alarm Monitor
Name Register No.
Setting
Range
Remarks
Warning IL02 Bit −
Alarm IL04 Bit −
Command Response Code IW08 0 to 8 04: Alarm Monitor
Command Status IW09 Bit
Bit 0 (Command execution
flag)
ON during execu-
tion
Bit 3 (Command error com-
pleted status)
ON when an error
occurs during
command pro-
cessing
Bit 8 (Command execution
completed status)
OFF during execu-
tion, and ON when
execution is com-
pleted.
M-III Inverter Command
Status
IL2A Bit Inverter operating status
M-III Command Status IW2C Bit Inverter command processing status
Inverter Alarm Code IW32 0 to FFFFH The currently occurring alarm is read out.