10.5 Motion Parameter Details
10.5.2 Setting Parameter List
10-43
OW14 Analog Output Terminal 1 Output
This data is enabled when the Inverter Drive Control
command is executed.
Unit: 10 V/4000 hex
Setting range: -16,384 (C000 hex) to 16,384 (4000
hex)
OW
15 Analog Output Terminal 2 Output
This data is enabled when the Inverter Drive Control
command is executed.
Unit: 10 V/4000 hex
Setting range: -16,384 (C000 hex) to 16,384 (4000
hex)
OW
16
Terminal Out-
put
Bit 0: Contact M1-M2
0: OFF, 1: ON
Outputs to terminals M1-M2.
This data is enabled when the Inverter Drive Control
command is executed.
Bit 1: Contact P1-PC
0: OFF, 1: ON
Outputs to terminals P1-PC.
This data is enabled when the Inverter Drive Control
command is executed.
Bit 2: Contact P2-PC
0: OFF, 1: ON
Outputs to terminals P2-PC.
This data is enabled when the Inverter Drive Control
command is executed.
Bits 3 to F Reserved
OW
17 PID Target
Unit: 0.01%
Setting range: -10,000 to 10,000
OW
18 Pulse Train Output
Unit: 1 Hz
Setting range: 0 to 32,000
OW
19 V/f Gain
Unit: 0.1%
Setting range: 20 to 2,000
OW
1A – Reserved
OW
1B
Command
Selection
Bit 0 Reserved
Bit 1: PID Target Enable
0: OFF, 1: ON
Turn ON this bit to enable the PID target set in
OW17.
Bit 2 Reserved
OW
1C
to
OW
31
– Reserved
OW
32 Inverter Alarm Monitor Number
Setting range: 0 to 3
Set the alarm history number for the Alarm History
Monitor command.
OW
33 Auxiliary Inverter Alarm Monitor Number
Setting range: 0 to 3
Set the alarm history number for the Alarm History
Monitor subcommand.
OW
34
to
OW3B
– Reserved
OW
3C Inverter User Constant Number
Setting range: 0 to FFFFH
Set the leading number of the user constants to
read by executing the Read User Constant com-
mand, or set the leading number of the user con-
stants to write by executing the Write User
Constant command.
Note: Set the register number used for MEMO-
BUS communications.
Continued on next page.
Continued from previous page.
Register No. Name Description