EasyManua.ls Logo

YASKAWA SVC - Page 558

YASKAWA SVC
623 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.5 Motion Parameter Details
10.5.3 Monitor Parameter List
10-56
IW31
M-III Sub Com-
mand Status
Bit 0 Reserved
Bit 1 Reserved
Bit 2: Command Ready
(CMDRDY)
ON when a subcommand can be received.
Bit 3 Reserved
Bits 4 to 7 Reserved
Bits 8 to B: Command
Error (CMD_ALM)
Reports the MECHATROLINK subcommand
error status.
Bits C to F Reserved
IW
32 Inverter Alarm Code
Range: 0 to FFFFH
Displays the alarm codes returned in the
response to the Alarm Monitor or Alarm History
Monitor command.
IW
33 Auxiliary Inverter Alarm Code
Range: 0 to FFFFH
Displays the alarm codes returned in the
response to the Alarm Monitor or Alarm History
Monitor subcommand.
IW
34
to
IW3B
Reserved
IW
3C Inverter User Constant Number
Range: 0 to FFFFH
Displays the inverter user constant number set
for the Read User Constant or Write User Con-
stant command.
IW
3D Reserved
IW
3E User Constant Reading Data 1
Range: 0 to FFFFH
Displays the value read out by executing the
Read User Constant command. Enabled when
Inverter User Constant Number Size
(OW3D) = 1 to 4.
IW
3F User Constant Reading Data 2
Range: 0 to FFFFH
Displays the value read out by executing the
Read User Constant command. Enabled when
Inverter User Constant Number Size
(OW3D) = 2 to 4.
IW
40 User Constant Reading Data 3
Range: 0 to FFFFH
Displays the value read out by executing the
Read User Constant command. Enabled when
Inverter User Constant Number Size
(OW3D) = 3 or 4.
IW
41 User Constant Reading Data 4
Range: 0 to FFFFH
Displays the value read out by executing the
Read User Constant command. Enabled when
Inverter User Constant Number Size
(OW3D) = 4.
IW
42 Auxiliary Inverter User Constant Number
Range: 0 to FFFFH
Displays the auxiliary inverter user constant num-
ber set for the Read User Constant or Write User
Constant subcommand.
IW
43 Reserved
IW
44 Auxiliary User Constant Reading Data 1
Range: 0 to FFFFH
Displays the value read out by executing the
Read User Constant subcommand. Enabled
when Auxiliary Inverter User Constant Number
Size (OW43) = 1 to 4.
Continued on next page.
Continued from previous page.
Register
No.
Name Description

Table of Contents