11.3 MECHATROLINK-III I/O Module Settings
11.3.4 I/O Command Details
11-18
Execution and Operating Procedure
1.
Make sure that the following condition is met.
2.
Set the I/O Command register to 1 to execute the Read Alarms/Warnings command.
Confirming Completion of the Command
Use the following information to confirm that the command has been completed.
No. Execution Condition Confirmation Method
1
I/O command execution must be com-
pleted.
Command Status bit 2 (CMDRDY) = 1
No. Confirmation Method
1 I/O Command Response register = 1 (Read Alarms/Warnings)
2 Command Status bit 2 (CMDRDY) = 1
3 ALM_RD_MOD is the same in the command and response.
4 ALM_INDEX is the same in the command and response.
If the command is not completed within 5 seconds after it is executed, bit 0 in the Master
Status register changes to 1 (TIMEOUT).
When bit 0 (D_ALM) or bit 1 (D_WAR) in the Command Status register is 1, check the error
details with the application and perform the stop processing. The system will not perform
stop processing.