11.3 MECHATROLINK-III I/O Module Settings
11.3.4 I/O Command Details
11-19
11
Appendices
Clear Alarms/Warnings Command
Clears an alarm or warning from the I/O Module.
Command Format
ALM_CLR_MOD: Clear Alarm Mode
0: Clears the current alarm or warning.
1: Clears the alarm history.
All other bits: Reserved for system.
Execution and Operating Procedure
1.
Make sure that the following condition is met.
2.
Set the I/O Command register to 2 to execute the Clear Alarms/Warnings command.
Confirming Completion of the Command
Use the following information to confirm that the command has been completed.
Output Registers Input Registers
7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
OW Clear Alarms/Warnings (= 2) IW Clear Alarms/Warnings (= 2)
Not used. Master Status
OW + 1
Command Control
IW + 1
Command Status
OW + 2
ALM_CLR_MOD
IW + 2
ALM_CLR_MOD
OW + 3 IW + 3
OW + 4 IW + 4
OW + 5 IW + 5
OW + 6 IW + 6
OW + 7 IW + 7
••
••
••
No. Execution Condition Confirmation Method
1
I/O command execution must be com-
pleted.
Command Status bit 2 (CMDRDY) = 1
No. Confirmation Method
1 I/O Command Response register = 2 (Clear Alarms/Warnings)
2 Command Status bit 2 (CMDRDY) = 1
3 ALM_CLR_MOD is the same in the command and response.
1. If the command is not completed within 5 seconds after it is executed, bit 0 in the Master Sta-
tus register changes to 1 (TIMEOUT).
2. When bit 0 (D_ALM) or bit 1 (D_WAR) in the Command Status register is 1, check the error
details with the application and perform the stop processing. The system will not perform stop
processing.
Important