11.3 MECHATROLINK-III I/O Module Settings
11.3.4 I/O Command Details
11-20
Read Parameter Command
Reads an I/O Module parameter.
Command Format
NO: Parameter Number
SIZE: Parameter Size (Bytes)
PARAMETER: Parameter Data
Execution and Operating Procedure
1.
Make sure that the following condition is met.
2.
Set the following parameters.
NO (Parameter Number)
SIZE (Parameter Size)
Setting Precautions
Make any necessary changes to NO (Parameter Number) or SIZE (Parameter Size) before executing
the Read Parameter command or during the same scan that the I/O Command register is set to 3. Do
not change these settings during execution of the Read Parameter command.
3.
Set the I/O Command register to 3 to execute the Read Parameter command.
Some I/O Module devices do not support the Read Parameter command. Refer to the product
specifications of the I/O Module for details.
Output Registers Input Registers
7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
OW Read Parameter (= 3) IW Read Parameter (= 3)
Not used. Master Status
OW + 1
Command Control
IW + 1
Command Status
OW + 2
NO
IW + 2
NO
OW + 3 SIZE IW + 3 SIZE
Not used. Not used.
OW + 4 IW + 4
PARAMETER Low
High
OW + 5 IW + 5
OW + 6 IW + 6
OW + 7 IW + 7
••
••
••
No. Execution Condition Confirmation Method
1
I/O command execution must be com-
pleted.
Command Status bit 2 (CMDRDY) = 1
Important