11.3 MECHATROLINK-III I/O Module Settings
11.3.4 I/O Command Details
11-23
11
Appendices
Read Non-volatile Parameter Command
Reads an I/O Module parameter from non-volatile memory.
Command Format
NO: Parameter Number
SIZE: Parameter Size (Bytes)
PARAMETER: Parameter Data
Execution and Operating Procedure
1.
Make sure that the following condition is met.
2.
Set the following parameters.
NO (Parameter Number)
SIZE (Parameter Size)
Setting Precautions
Make any necessary changes to NO (Parameter Number) or SIZE (Parameter Size) before executing
the Read Non-volatile Parameter command or during the same scan that the I/O Command register
is set to 5. Do not change these settings during execution of the Read Non-volatile Parameter com-
mand.
3.
Set the I/O Command register to 5 to execute the Read Non-volatile Parameter com-
mand.
Some I/O Module devices do not support the Read Non-volatile Parameter command. Refer to
the product specifications of the I/O Module for details.
Output Registers Input Registers
7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
OW
Read Non-volatile
Parameter (= 5)
IW
Read Non-volatile
Parameter (= 5)
Not used. Master Status
OW + 1
Command Control
IW + 1
Command Status
OW + 2
NO
IW + 2
NO
OW + 3 SIZE IW + 3 SIZE
Not used. Not used.
OW + 4 IW + 4
PARAMETER Low
High
OW + 5 IW + 5
OW + 6 IW + 6
OW + 7 IW + 7
••
••
••
No. Execution Condition Confirmation Method
1
I/O command execution must be com-
pleted.
Command Status bit 2 (CMDRDY) = 1
Important