ProfiMessage
Selection Description
Invalidvalue Invalidvalueinmonitoredchannel
Measuringrange
overrun
ThemeasuredvalueisabovetheA/Dconverter
measuringrange
Measuringrange
underrun
ThemeasuredvalueisbelowtheA/Dconverter
measuringrange
Hardwareerror Errorinthehardware
Simulatedvalue
Aninternallygeneratedvaluefortesting,for
examplefromthePROFIBUS
Nonumber(NAN=
NotANumber)
Acalculationhasnotreturnedavalidnumber,for
examplerootofnegativenumbers
Infinitevalue
Acalculationisinfinite,forexampledivisionby
zero
Defaultvalue Defaultvalueformonitoredchannel
Forcedvalue
Theforcedvalueisreplacementvalue,for
examplewhereasensorhasafaultyanalogue
channel
Scalerangeoverrun Scalingrangeexceeded
Scalerangeunder-
run
Scalingrangenotmet
Generalwarning
Anerroroccurredduringdatatransmission,for
exampleduringthePROFIBUStransfer
Triggerblockend Endofatriggerblock(datastorage)
Inputvalueoutside
thepermissible
range
Thesourcechannelvaluecannotbeprocessed,
thereisaparametererror
4.7.24 Stopwatch
Example 1
Setting:Start /StopatHigh level,Reset at startisenabled.
146
Delphin Technology AG
Dezember 2015
ProfiMessage Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delphin ProfiMessage and is the answer not in the manual?

Delphin ProfiMessage Specifications

General IconGeneral
BrandDelphin
ModelProfiMessage
CategoryTest Equipment
LanguageEnglish