EasyManua.ls Logo

Delphin ProfiMessage - 9.2.3 Time signal; 9.2.3.1 Digital filter; 9.2.3.2 Digital integrator

Delphin ProfiMessage
322 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ProfiMessage
9.2.3 Timesignal
EveryvibrationsignalrecordedisinitiallysavedtothebufferoftheI/Omodule.
Theanalogueinput”channeldeliversablockofmeasurementdata(e.g.2048
amplitudevaluesovertime).Thisblockisreferredtoasatimesignal.
Properties
l 128to8192samples,sampledsynchronously/inparallelat256Hzto20480
kHz
l Variablepre/posthistoryand/ortriggerpoint
l Digitalfilters,integratorsetc.canbeused
l Datacompressioncanbeusedfortransmissionandstorage.
Topics
9.2.3.1 Digitalfilter
Properties
l Choiceoffiltertype:low-pass,band-pass,high-passordemodulationfilter
l Filterordersof28,presetButterworthcharacteristic
l Adjustablecut-offfrequencyintherange1Hz10kHz
l Adjustablefiltersforeachchannel
Application
High-frequencyinterferencesarefilteredoutoftheacquiredsignal.Oronlythe
desiredfrequencyrangeisfilteredoutforanalysis.
Restrictions
Thedigitalfiltersarealsosubjecttotheserestrictionsifapplicable:
l BoardV2.00toV2.12
For1...4analogueinputs:allfiltersavailable,max.orderis8.
For5...8analogueinputs:onlylow-passisavailable,max.orderis4.
l BoardV2.13andhigher
For1...8analogueinputs:allfiltersavailable,max.orderis6.
9.2.3.2 Digitalintegrator
Properties
l Numericalintegrationoftherecordedvibrationsignal
l Fixedscalingfactorpresetat1000.
Application
257
Delphin Technology AG
Dezember 2015
ProfiMessage Manual

Table of Contents