ProfiMessage
IfaModbususersendsvaluesthatrequireconversion,enableScaling andenter
Min/MaxvaluestoconvertfromtheInput value totheScalevalue.
IftheUsechannelasoutputoptionisused,scalingtakesplaceintheoppositedir-
ection:EntertherangefromthesourcedatainScalevalueandtherangeforthe
outputsignalinOutput value.
Withoutscaling,thechannel'sData typeisusedWhenscalingis
enabled,thefloatingdatatypeisalwaysusedforthechannel.
Thisalsoapplieswhenthechannelisusedasanoutput:Whenscal-
ingisenabled,thechannelmusthavethefloatingdatatype,oth-
erwiseyouhavetousethetypeunderData type.
Scaling example
Intheaboveimage,aconversiontakesplacefrom2000(integervalue)to200
C),i.e.itreturnsadecimalpointdespitetransmissionofaninteger(wholenum-
ber).
Using the channel as output
IfyoucreateaModbuschannelasanoutput,youcansenddatafromtheDelphin
devicetootherModbususers.
EnterthedataforthemessagetobesentinasimilarwaytoaModbusinput.You
mustalsoentertheSource(ofthesignal).
EntereitheraconstantfortheSource(Manual value)orselectChannelandan
existingchannelinthedeviceforwhichavalueistobeoutput.SelectingApplic-
ationenablestheoutputvaluetobemanuallysetviatheDataServiceConfigurator
orautomaticallysetviaaProfiSignalapplication.Thesourcetypeisconvertedto
thetypegiveninData type(referalsotoScaling).
Inherit status(forChannelsettingsonly):Thestatusoftheinputchannelisused,
butnotoutputtotheCANbus.
Set asynchronous:Whenthisoptionisenabledtheoutputvaluetransmitsassoon
asthevaluechanges,thatis,inreal-time.Otherwiseanewvalueistransmitted
withthenextcycle.
4.8.3.4 User-definedprotocol
WerecommendgivingauniqueChannel name,amendingtheDescription and,if
necessary,enteringaLocation.TheMain settingstabisdescribedinthefollowing
andthenhowinputandoutputchannelsarecreated.
Main settings tab
189
Delphin Technology AG
Dezember 2015
ProfiMessage Manual