ProfiMessage
Masterandslavesettingsareidentical.
Setting guidelines
1. Digitalinput4anddigitaloutput4areusedinternallyforsynchronisation.
Bothchannelsshouldbesettoinactive.TheSource valueshouldbesetto
manualvaluefordigitaloutput4.
2. Theconfigurationtothe“master”mustbemanuallychangedonlyaftercon-
figurationtothe“slave”ismanuallychangedsothatthehandshakestaysin
step.
3. Ifnoexternaltriggersignalisused,thetimeperiod(withthemaster)must
besetlargerthanthenaturalcycle(recordingtime+computingtime+2x
measurementdatatransmissiontime)sothatthehandshakestaysinstep.
Seetimingdiagram.
Procedure
252
Delphin Technology AG
Dezember 2015
ProfiMessage Manual