3 Devices
DVP-20PM Application Manual
3-39
Setting the
polarities of
the input
terminals
D1804
If users want to turn an input terminal into a Form A contact, they have to set the bit
corresponding to the input terminal to ON. If the users want to turn an input terminal
into a Form B contact, they have to set the bit corresponding to the input terminal to
OFF.
Bit# Polarity of an input terminal of the Z-axis
0 PG2
1 B1
2 A1
3 LSN2
4 LSP2
5 DOG2
Reading the
states of the
input terminals
D1805
If a bit in D1805 is ON, the input terminal corresponding to the bit receives a signal. If a
bit in D1805 is OFF, the input terminal corresponding to the bit does not receive a
signal.
Bit# State of an input terminal of the Z-axis
0 PG2
1 B1
2 A1
3 LSN2
4 LSP2
5 DOG2
Setting a filter
1. Users can set the hardware filter for the input ter
minals START, STOP, DOG,
LSN, LSP, and PG by means of D1806.
coef
ficie
the inp
terminals
nt for
ut
2. Users can set a filter coefficient for the input terminal MPG0/1 by setting the high
byte in D1806.
D1806
3. Filter coefficeint
4N
2
85000
(kHz); N=1~19
N kHz N kHz
1 2656.25 11 2.593994
2 1328.125 12 1.296997
3 664.0625 13 0.648499
4 332.0313 14 0.324249
5 166.0156 15 0.162125
6 83.00781 16 0.081062
7 41.50391 17 0.040531
8 20.75195 18 0.020266
9 10.37598 19 0.010133
10 5.187988
4. If the value in D1806 is 0, no signals will be filtered.
5. If the value in D1806 is H0A0A, the filter coefficient for START, STOP, DOG,
LSN, LSP, and PG
5.187988
2
85000
410
, and the signals whose frequencies are
higher than 5.187988 kHz will be removed.
O100 error
1. If an error occurs
in O100, M1953 will be ON, the error code corresponding to the
error will be stored in D1802, and the step address at which the error occurs will
be stored in D1803.
M1953, D1802,
and D1803
2. Please refer to appendix A in chapter 15 for more information about error codes.