Page 10
Fire Alarm Computer 8000C / M
Delay
Yellow LED lights
An on/off switching interval has been programmed for the delay
function.
During this time, the activating of the master box (MB) due to a
fire alarm is automatically delayed by the delay time
programmed in the customer data base.
Yellow LED blinks
An alarm signal has been detected during the active delay time
and the programmed delay time (max. 600 seconds, according
to programming) has been initiated.
The master box is activated after expiry of this time.
Verify
Yellow LED lights
The function Verify has been activated by the Verify/Buzzer off
key. The programmed Verify time (max. 600 seconds) for the
Verify of the cause of the alarm is running.
The master box is only activated after the expiry of the Verify
time.
The function delay/Verify is described in Section 4.7.