Fire Alarm Computer 8000C / M
Page 159
25.1 Installer level; Primary loop function
Primary loop function
Under this menu point, the internal primary loops of this fire alarm control panel or other fire alarm
control panels 8000C / M in an essernet
®
network can be switched on or off and checked by a
manual test function.
Additionally, it is possible to replace single detectors in operative analog loops, (e.g. during
maintenance work) without changing the Customer data programming with the service PC.
Primary loops are:
the Analog loop module, including all connected analog detector zones and esserbus
®
transponders
all analog ring modules included in this FACP
(including the analog loop connected to this module with all bus devices)
the 4-zone module, including all connected fire or diagnostic detector zones (EDD). For this
module, the menu points Detector replacement and Test are inoperative.
all four-zone-modules included in this FACP
(including all detector zones and detectors connected to this module)
certain modules, such as relays or the interface on the basis/peripheral module
Definition of the Primary loop number
Individual assemblies of the FACP 8000C / M can be switched on/off with the internal primary loop
number through the control panel keyboard or programmed with the customer data editor. This
internal primary loop number is composed of the control panel number, the slot and the assembly
number.
Example: FACP 8000C / M (Panel number 01)
1
2
B
1
2
3
4
5
D
B
Fig. 6: Example FACP 8000C Example FACP 8000M
Commissioning / Servicin
g
P
rimary loop number 0123
P
rimary loop number 0113
P
rimary loop number 0131