Fire Alarm Computer 8000C / M
Page 185
27.1 Trouble messages in the display
Up to three works-programmed trouble messages with 8 characters each can be displayed in the
second line of the display. If a clear text trouble message applying to an event is displayed, this
trouble message is shown automatically in the display or can be activated with the function key
Param/AT
.
Trouble
text
possible cause 1st measure 2nd measure
UBext
UB
ext
fuse blown. Short
circuit in UB
ext
supply
voltage
Check whether fuse blown
or short circuit
---
UBint
supply voltage Short circu
in UB
int
supply voltage
Check whether fuse blown
or short circuit
---
ULine
U
line
fuse blown
Check fuse and replace if
necessary
---
short
Brief loss of mains power
Check mains supply and
mains fuse
---
long
Loss of mains power
Check mains supply and
mains fuse
---
ext. PSU
Failure of supplementary
external power supply
Check external power
supply unit
Check monitor line
paper out
The internal printer has ru
out of paper
Replace the printer paper
roll
---
not ready
The paper retaining lever
has not been returned to
its original position after
paper change
Set lever to correct
position
---
not voltage
The internal printer has no
supply voltage
Check wiring of UB
ext
and
fuse
---
short cct.
A short circuit has been
detected in the
corresponding primary
loop
Check the indicated
primary loop (see Prloop
No.)
---
short/open
A short or open circuit has
been detected in the
corresponding primary
loop
Check the indicated
primary loop (see Prloop
No.)
---
com. err.
A communications error
has been detected in the
corresponding primary
loop
Check detector contacts,
replace detector and/or
necessary module if start-
up
---
start-up
An error has been
detected when an analog
ring loop was switched on
normal operation is
impossible
Localise the source with
the service
program92GRAF or
92TOOLswitch on or
reconfigure the analog ring
loop
---
Trouble message