Fire Alarm Computer 8000C / M
Page 149
24.13 esserbus
®
transponder eK-12-REL
12 freely programmable, potential-free relays, either NC contact or NO contact
Switching power : < 30 V DC/ 1A per relay
External switching voltage,
capable of being monitored : 12 V DC or 24 V DC
24.14 esserbus
®
- transponder eK-32AE
32 freely programmable outputs for activating light-emitting diodes (LED), such as in a remote
indicating panel.
Switching power : 12 V DC / 10 mA per output
External switching voltage,
capable of being monitored : 12 V DC
Lamp test function for checking the indicator LED
24.15 esserbus
®
- transponder eK-1GRP
1 input for connecting a non-addressable fire detector zone
External voltage supply : 10,5 V DC to 28 V DC
Rated voltage : 12 V DC or 24 V DC
Power consumption : max. 28 mA
Detector zones voltage : 9 V DC
Line length in detector zone : max 1000m
External switching voltage,
capable of being monitored : 12 V DC or 24 V DC
Technical Da