Page 166
Fire Alarm Computer 8000C / M
25.1.4 Simulation of detector states
Under this menu point, the state of addressable detectors of the Series 9100 and 9200 (no
esserbus
®
transponder) can be simulated for test purposes. In all non-addressable detectors, the
detector zone state is simulated.
With the simulation of a detector state for test purposes, all programmed displays and controls
corresponding to this detector and state in the Customer data of the fire alarm control panel are
activated.
☞
This function pertains exclusively to the detectors of this (local) control panel. The
simulation of detector states in the essernet
®
network is impossible.
☞
Simulation of individual detectors or zones is not supported via communications
transponder 788615 of the 8010 releasing control system.
Self-control of the intelligent fire detectors Series 9200
An intelligent fire detector can be operated in connection with a detector base output (relay or
open collector). If a control has not been programmed in the Customer data of the fire alarm
control panel for this detector, the integrated detector base output is activated during the
simulation of the "Alarm" state.
Fig. 10: Entering the zone and detector number
By pressing the
Repeat
key, the displayed detector number is incremented by the value "+1
without the need of entering the number of the new (next higher) zone/detector number o
the keyboard.
☞
Dependant on the programming of the control panel, the master box and any other external
alarm devices are activated during the state simulation of a fire detector!
ommissioning / Servicing