Fire Alarm Computer 8000C / M
Page 115
12.2 Analog loop module esserbus
®
-PLus (Part no. 804382)
This module provides the "esserbus
®
-PLus" loop mode, e.g. for direct connection of audible loop
devices. Note that the esserbus
®
-PLus operation requires special components and panel settings
(see Chapter "esserbus
®
-PLus function"). Mixed operation of Standard and esserbus
®
-PLus
function is not
possible !
esserbus
®
-Plus connection
Released cable terminal:
Press in upper tab and fit cable below.
Do not use other analog loop modules if the analog loop voltage setting is 42 V fo
esserbus
®
-PLus (see power supply module). Damage to the system possible !
X 1
64-way plug connector to micro module slot of the basic module, field device module or
extension module of the FACP 8000C / M
K1,K 2
Bi-directional loop interrogation by loop isolators
(K1 = A+, A- / K2 = B+, B-)
LED 1
(SMD)
red flashing
⇒
+42V supply voltage failure or communication to
control panel processor interrupted
red lit steadily
⇒
Module in CPU failure mode
(control panel CPU failure)
LED 2
(SMD)
yellow flashing
⇒
Processor program running - normal mode
yellow flashing rapidly
⇒
Module in test mode
LED3
(SMD)
red lit steadily
⇒
esserbus
®
-PLus Mode activated
42 V loop voltage
LED4
(SMD)
yellow flashing
⇒
Module reset
yellow lit steadily
⇒
Module defect
LED 5
(SMD)
red flashing
⇒
in normal mode in time with communication on the loop
red lit steadily
⇒
Short circuit on analog loop
Analog loop modu
04382