4.4 Detectors
Functions relating to detectors are only possible for addressable fire detectors of the ESSER
detector series 9100 and 9200. These fire detectors can be selected and controlled by a detector
address.
4.4.1 Switching on / resetting a detector
With switch-on, an individual disconnected detector of the selected detector zone is switched into
the operative status or an active detector is reset and any imminent messages such as Fire or
Trouble for this detector are deleted.
Please note that the zone number has to be entered before the detector number.
Press Key
Detector
Zone
2 1
On
2
Fig. 23: Switching on detector zone 2 /detector 12 (example)
Fig. 24:Display switching on detector zone 2 / detector 12
Detectors
Operation
on
in progress
Zone: 2
Detector: 12