Fire Alarm Computer 8000C / M
Page 161
25.1.1 Switching on / resetting a primary loop
Fig. 7: Switching on / resetting a primary loop
♦
Enter the number of the primary loop to be switched on and press the
Select
function key
♦
Enter the number of the desired function (1 = Switching on/reset) or select the menu options
Switching on/Reset
with the cursor keys and press the
Function
key
The primary loop is switched on and indicated on the display with a alphanumeric message.
Switching off a primary loop
♦
Enter the number of the primary loop to be switched off and press the
Select
function key
♦
Enter the number of the desired function (2 = Switching off) or select the menu options
Switching
off with the cursor keys and press the
Function
key
The primary loop is switched off and indicated on the display with a alphanumeric message. In the
switched off state of a primary loop, the yellow LED
Collective switch-off
lights in addition to the
display message. The displays and controls programmed in the Customer data of the fire alarm
control panel for the function Switch-off are activated.
When a primary loop is switched off, for example the 4-zone module or the analog loo
module, all detector zones and fire detectors connected to this module are also switche
off.
Switched off fire detectors will not signal an alarm in the case of an event !
Commissioning / Servicin
Primary loop / transfer route