Page 146
Fire Alarm Computer 8000C / M
24.3 RS 232/TTY module (serial interface)
Total power consumption (TTY) : approx. 55 mA
Total power consumption (RS 232) : approx. 35 mA
Transmission speed : max. 19200 bit/s
24.4 4-output module
Connection voltage : 4V - 35V (DC)
Output current : max. 300 mA per output
Max. permissible total current : 1 A
Total current consumption : ca. 15 mA
24.5 7-output module (open collector outputs)
Connection voltage : 4V - 35V (DC)
Output current : max. 300 mA per output
Max. permissible total current : 1 A
Total current consumption : ca. 15 mA (all 7 channels switched)
24.6 Master box activation module
Total power consumption
without monitoring : 10 mA
Monitored : 15 mA
Contacts : 1 change-over contact
Switching current : 1 A
Switching voltage : max. 30 V DC
" Reset MFAB“ output : max. 300 mA (+12V bzw.+24V DC) short-circuit resistant
" Reset MFAB " output : max. 300 mA short-circuit resistant
Fuse F1 : Multifuse 1,1 A (on operating panel control card)
T
echnical Data

Table of Contents