Fire Alarm Computer 8000C / M
Page 41
5.1.1 Primary loop functions
Using this function, primary loops including all connected zones and loop devices can be switched
on or off at the keypad.
The switching state is indicated on the control panel and the alphanumeric display.
Fig. 44: Entering the primary loop number
♦
all analog loop modules included in this FACP
(including the analog loop with all associated devices connected to this module)
♦
all 4-zone-modules included in this FACP
(including all detector zones and detectors connected to this module)
♦
certain modules such as relays or the interface on the basic/peripheral module
Switch on / disconnect Primary loops:
♦ Enter the number of the primary loop which is to be switched on and press the Select function
key
♦ Enter the number of the desired function (1 = switch on/reset, 2 = switch off) or select the menu
point with the cursor keys and press the Function key
In the case of an input error, the display can be erased by pressing the Zone key and the primary
loop number can be re-entered.
!
When a primary loop, for example a 4-zone module or an analog loop module is
disconnected, all zones and loop devices connected to this module are disconnected.
Disconnected fire detectors and call points will not activate an alarm in the case of an
event.
Service Level
Primary loop / Transfer route
Primary loop :
Func. menu Repeat Select
1 on / off
2 reset