Fire Alarm Computer 8000C / M
Page 107
15 Technical Data
Mains voltage
230 V AC
Rated frequency
50 – 60 Hz
Rated current
0,35 A
Current for external users
max. 2A
Permissible current consumption
with 2 x 24 Ah batteries and 72
hour emergency power supply
max. 650 mA
Battery charge voltage
Over-discharging protection
13.9 V DC , at 25 °C ambient temperature
9.5 V DC,
switch-off threshold activation by means of jumper
Ambient temperature
-5 °C to +50 °C
Ambient conditions
IEC 721-3-3:1994, class 3k5.
Protection class
I
VdS approval
G 296006
Basic module
Capability of operating after CPU
failure
yes, supply via +5V DC internal
TTY interface
20 mA, max. cable length 1000m
Common trouble relay
contact rating max. 30 V DC / 1A
Quiescent current
150 mA (incl. operating panel card and power supply)
Field device module
One micro module slot with 8-pole terminal card.
Quiescent current
ca. 10 mA (without micro module)