Page 150
Fire Alarm Computer 8000C / M
24.16 esserbus
®
transponder eK-4 IN/2OUT
4 inputs for connecting four non-addressable fire detector zones plus two freely programmable
relay outputs or as a BSL interface. For programming as a BSL interface, the customer data editor
and FACP software version V2.38 are required.
External voltage supply : 10,5 V DC to 28 V DC
Rated voltage : 12 V DC or 24 V DC
Power consumption : max. 28 mA
Detector zone voltage : 9 V DC
Line length in detector zone : max 1000m
Relay / contact rating : 30 V DC/ 1A or 48 V DC/0,5A
External switching voltage,
capable of being monitored : 12 V DC or 24 V DC
24.17 esserbus
®
transponder eK-KOM-LMST
Communications transponder for the 8010 fire alarm and extinguishing computer. For connection
to the analogue analog loop.
Analogue analog loop : nominal current: < 150 mA
Ext. power supply : quiescent current: < 3 mA, supplied by the 8010
fire alarm and extinguishing computer
Mounting location : Inside the housing of the 8010 fire alarm and
extinguishing computer
Software requirements : customer data editor, fire alarm system 8000,
version 2.38 or higher
FACP software : version 2.38 or higher
echnical Data