Fire Alarm Computer 8000C / M
3 Operating status of the fire alarm control panel
The current operating status of the fire alarm control panel 8000C / M is shown on the operating
panel. Six different operating conditions are possible:
3.1 Normal condition
The normal condition refers to an operative monitoring state of the control panel unchanged by
external influences.
The green LED in Operation lights.
No further displays or messages.
The operating panel keyboard is locked by the key switch.
3.2 Fire
The control panel is in alarm mode, i.e. it is signalling a fire alarm.
The common display FIRE (red LED) lights.
The master box (MB) has been activated.
The internal control panel buzzer sounds.
External alarm devices, e.g. acoustic alarm devices or control panel buzzers are activated.
The zone which has detected the fire is shown in the display with the programmed additional
text.
The red LED of the corresponding zone(s) lights in the single zone indicator units (optional). If
several zones signal a fire alarm, the red LED of the zone which first detected the fire blinks
(initial alarm detection).
The red LED Master box (MB) lights when a master box for automatic transmission of the alarm
is connected and the fire department has been informed.
Possibly, the red LED Notify fire department may light. The fire department has not been
informed via the master box.
Call the fire department immediately!
Operating status of the fire alarm control panel