Fire Alarm Computer 8000C / M
Page 37
4.7.1 Delay
By pressing the Delay key, the function Delay is started or ended manually (toggle function). The
activated delay function is indicated on the operating panel by the continuously illuminated yellow
LED delay.
Fig. 38: Delay key
If a fire alarm occurs when the delay function is activated, the activation of the master box (MB) is
delayed by the delay time programmed in the customer data (max. 600 seconds). The initiated
delay time is indicated in the operating panel by the blinking yellow LED.
4.7.2 Verify
If the delay time has been started due to a fire alarm, the activation of the master box can be
delayed additionally to the delay time (max. 600 seconds) by the verification time (max. 600
seconds) for the Verify of the cause of the alarm by pressing this key.
Fig. 39: Verify key
VdS
The guidelines of the Association of German Property Insurance Companys (Verband der
Schadenversicherer VdS, Cologne) must be observed for the function Delay and Verify.
Delay and Verify
Delay
Verify