Fire Alarm Computer 8000C / M
Page 23
4.1.2 Display priority of the messages in the display
Additional
Messages
Fig. 13: Additional Message Key
Display priority
The first and last message with the highest current priority are shown in the alphanumeric display
of the Fire alarm control panel 8000C / M respectively. If several messages with equal priority are
imminent, these can be queried by pressing the key Additional Messages.
Priority stage Condition Display
1
Fire alarm
FIRE
2
Fire alarm primary loop
FIRE
3
Technical alarm
T-ALARM
4
Pre-alarm
PRE-ALARM
5
Trouble
TROUBLE
6
Trouble primary loop
LINE TROUBLE
7
Transfer route switched on (Primary loop)
LINE ON
8
System trouble
SYS TROUBLE
9
Disconnection
DISCONNECTION
10
Disconnection primary loop
LINE OFF
11
Trouble relay output AE
TROUBLE
12
Switch-off relay output AE
O/P OFF
13
Activate AE
ACTIVATE
14
Testmode
TEST
☞
If the control panel is operated during the display, the corresponding function is carried out.
The message with the highest priority reappears in the display automatically approx. 20
seconds after the last key has been pressed.