Fire Alarm Computer 8000C / M
Page 145
24 Technical Data
24.1 esserbus
®
Analog loop module (Part no. 784382)
Recommended connecting
cable
: Line transmission cable IY-St-Y; 0.8 mm cable cross
section
Max. analog loop resistance 75
Ω
with 0.8 mm cable cross
section(measured from A+ to B+) 130
Ω
with 0.6 mm cable
cross section
These values correspond to a total length of a analog loop
of approx. 2000m
Power consumption : 25 mA
Short-circuit current limit : 60 mA
CPU-failure function : Processor with capability of operating in CPU failure mode
Internal voltage supply : +12V and +26 V via connector strip
24.2 esserbus
®
-PLus Analog loop module (Part no. 804382)
In esserbus
®
-PLus Systems with addressable audible loop devices the number of analog loops is
limited to 4. No more than 4 analog loop modules (Part-no. 804382) should be installed per panel.
Recommended connecting cable
Line transmission cable IY-St-Y; 0.8mm cable cross section
Max. ring loop resistance 75
Ω
with 0.8 mm cable cros
section (measured from A+ to B+) 130
Ω
with 0.6 mm cabl
cross section
The maximum loop length depends on the number and typ
of the audible alarm devices and may be less than th
absolute maximum of 2000m.
Power consumption
25 mA
Short-circuit current limit
65 mA (normal), 280 mA (alarm)
CPU-failure function
Processor with capability of operating in CPU failure mode
Internal voltage supply
+12V and +42V via connector strip
Technical Da