Fire Alarm Computer 8000C / M
Page 165
Type/extent of the detector replacement Without
service PC
displayed
trouble
code*
The type and external switching of the exchanged detector are i
conformance. For example, if a defective OHI-detector without
detector base output is replaced with a new OHI-detector without
detector base output
yes ---
The detector type changes , the external switching remains th
same. For example, an optical smoke detector is replaced with a
OHI- detector and the existing external wiring is not changed.
yes
St : 081-087
095
During the replacement of detectors, the external switching
removed; the detector type remains unchanged. For example, a
OHI-detector with a relay output is replaced with an OHI-detecto
without a relay output. The change in the external switching from
relay to LED outputs (or the converse) is not recognised.
no St : 088
During the replacement of detectors, the external switching is added
the detector type remains unchanged. For example, an OHI-detecto
without a relay output is replaced with an OHI-detector with a rela
output. The change in the external switching from relay to LE
outputs (or the converse) is not recognised.
yes St : 089
An isolating circuit is removed, the detector type remain
unchanged. For example, an OHI-detector with an isolating circu
(zone isolator) is replaced with an OHI-detector without an isolatin
circuit.
no St : 088
An isolating circuit is inserted, the detector type remains unchanged
yes St : 090
The wiring of the analog loop is changed. For example, during th
replacement of detectors, a new detector is inserted in an additiona
spur loop.
no St : 066
Replacement of identical esserbus
®
transponders. A defectiv
esserbus
®
transponder Type 12 relay is replaced with an identica
esserbus
®
transponder. The programming of the 12 relay outputs
not changed.
yes ---
Replacement of dissimilar esserbus
®
transponders. An esserbus
®
transponder is replaced by another type or the designation
programming of the outputs is changed.
no St : 080
Replacement of an esserbus
®
transponder with an automat
detector and the converse
no St : 080
Replacement of a manual call point with an esserbus
®
transponde
and the converse.
no St : 080
*
possible in the installer level of the fire alarm control panel
.
Commissioning / Servicin