EasyManua.ls Logo

Esser 8000C - Page 165

Esser 8000C
190 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fire Alarm Computer 8000C / M
Page 165
Type/extent of the detector replacement Without
service PC
*
displayed
trouble
code*
The type and external switching of the exchanged detector are i
n
conformance. For example, if a defective OHI-detector without
a
detector base output is replaced with a new OHI-detector without
a
detector base output
yes ---
The detector type changes , the external switching remains th
e
same. For example, an optical smoke detector is replaced with a
n
OHI- detector and the existing external wiring is not changed.
yes
St : 081-087
/
095
During the replacement of detectors, the external switching
is
removed; the detector type remains unchanged. For example, a
n
OHI-detector with a relay output is replaced with an OHI-detecto
r
without a relay output. The change in the external switching from
relay to LED outputs (or the converse) is not recognised.
no St : 088
During the replacement of detectors, the external switching is added
,
the detector type remains unchanged. For example, an OHI-detecto
r
without a relay output is replaced with an OHI-detector with a rela
y
output. The change in the external switching from relay to LE
D
outputs (or the converse) is not recognised.
yes St : 089
An isolating circuit is removed, the detector type remain
s
unchanged. For example, an OHI-detector with an isolating circu
it
(zone isolator) is replaced with an OHI-detector without an isolatin
g
circuit.
no St : 088
An isolating circuit is inserted, the detector type remains unchanged
.
yes St : 090
The wiring of the analog loop is changed. For example, during th
e
replacement of detectors, a new detector is inserted in an additiona
l
spur loop.
no St : 066
Replacement of identical esserbus
®
transponders. A defectiv
e
esserbus
®
transponder Type 12 relay is replaced with an identica
l
esserbus
®
transponder. The programming of the 12 relay outputs
is
not changed.
yes ---
Replacement of dissimilar esserbus
®
transponders. An esserbus
®
transponder is replaced by another type or the designation
/
programming of the outputs is changed.
no St : 080
Replacement of an esserbus
®
transponder with an automat
ic
detector and the converse
no St : 080
Replacement of a manual call point with an esserbus
®
transponde
r
and the converse.
no St : 080
*
possible in the installer level of the fire alarm control panel
.
Commissioning / Servicin
g

Table of Contents