Page 184
Fire Alarm Computer 8000C / M
Trouble
code no.
Possible cause 1st measure 2nd measure
086
A TD-detector has been
installed at detector
location. The detector type
has changed in
comparison with the
customer data
Check whether detector
type change is desired; if i
is, activate analog loop.
Otherwise install detector
you require and re-start
Detector change
087
A TD-detector has been
installed at detector
location. The detector type
has changed in
comparison with the
customer data
Check whether detector
type change is desired; if i
is, activate analog loop.
Otherwise install detector
you require and re-start
Detector change
088
Detector circuitry has been
changed at detector
location. Now detector has
neither external circuit
(relay / LED) nor isolating
relay.
If this change is not
desired, connect service
PC and run a configuration
check. Re-programm
customer data.
---
089
Detector circuitry has been
changed at detector
location. Now detector has
external circuit. (relay /
LED)
Check whether this
detector location is to have
an external circuit. isolating
relay. If it is, activate loop.
Otherwise install detector
you require and re-start
Detector change
090
Detector circuitry has been
changed at detector
location. Now detector has
an isolating relay
Check whether this
detector location has an
isolating relay. If it has,
activate loop.
Otherwise install detector
you require and re-start
Detector change
095
A O
2
T-detector has been
installed at detector
location. The detector type
has changed in
comparison with the
customer data
Check whether detector
type change is desired; if i
is, activate analog loop.
Otherwise install detector
you require and re-start
Detector change
☞
Ionization smoke detector or fire detector with ionization sensor may only be opened by
authorized persons with handling license issued under the Radiation Protection Ordinance
(German: Strahlenschutzverordnung - StrSchV).
eaning of the three-digit trouble code