Fire Alarm Computer 8000C / M
Page 101
Operating mode: positive switching (+12 V DC
intern
/ max. 1A), not monitored
+12V DC Ub int.
RÜC
GND
Fig. 44: Terminal of the master box relay K1
Operating mode: not monitored change-over contact
RÜCK
GND
Fig. 45: Terminal of the master box relay K1
External voltage: < 30 V DC, max 1 A
The 8000C / M FACP's relays may only be connected to DC voltages. No AC voltage ma
be applied, not even when a relay is programmed as a
non-monitored change-over contact.
Field device modu