Fire Alarm Computer 8000C / M
Trouble
code no.
Possible cause 1st measure 2nd measure
010
An electrically leading
substance caused a short-
circuit in the I-chamber
Clean I-chamber and
92TOOL or 92GRAF chec
k
with the diagnosis
software. Noticing salt or
fraying deposits.
Replace detector and
return to ESSER.
011
Sensor is soiled with
conductive substance.
Clean detector and check
it
with the diagnosis software
92TOOL or 92GRAF
Using an other detector
type.
012 Detector is soiled or damp
Check whether detector is
installed in a damp
environment.
Check the installed
detector if the surrounding
area is humid. Use
protective measures if
necessary, e.g. surface
mount adapter 781495 or
781497/98 uses base
adapter
013
1) Air speed too high at
site of installation.
2) Detector is soiled with
conductive substance
and may be installed in
damp environment.
Clean detector and check
it
with the diagnosis software
92TOOL or 92GRAF
Using an other detector
type.
014
Short-circuit at the
temperature sensor
Return faulty detector to
ESSER
---
015
1) Faulty bonding of the
temperature sensor.
2) First installation at a
cool place.
Clean detector and check
it
with the diagnosis software
92TOOL or 92GRAF
Replace detector and
return to ESSER.
016 see 001 --- ---
017
018
1) Detector is soiled with a
conductive substance o
r
installed in damp
surroundings.
2) Faulty detector
Clean detector and check
it
with the diagnosis software
92TOOL or 92GRAF
Replace detector and
return to ESSER.
019
Detector is soiled with oily
substance.
Clean detector and check
it
with the diagnosis software
92TOOL or 92GRAF
---
M