Fire Alarm Computer 8000C / M
Page 79
X1
plug connector for transformer (secondary)
F1
fuse for the FACP internal supply power to the analog loop T 4 A
F2
fuse T 8 A at 150 VA
Caution!
In order to prevent a short-circuit between the secondary voltage of the transformer an
the heat sink the plastic cover must always be fitted on top of the glass fuse (F2).
BR1
standard 771690
automatic ground fault detection
(factory standard setting = ON)
automatic ground fault detection
disabled
esserbus
®
-PLus 802426
automatic ground fault detection disabled
(factory standard setting = OFF)
automatic ground fault detection
battery discharge protection (U
batt
< 9.5 V DC)
discharge protection enabled (factory standard setting)
BR2
discharge protection disabled
BR3
jumper for selecting the internal analog loop voltage
standard systems: 27.5 V analog loop voltage
esserbus
®
-PLus
systems:
42 V
analog loop voltage, part no. 804383
required for esserbus
®
-PLus functionality.
Mixed operation with standard and esserbus
®
-PLus functionality is not possible.
maximum of 4 analog loop modules, part no. 804383
may be fitted in a esserbus
®
PLus system with a loop voltage of 42 V.
R 3
potentiometer for adjusting the battery charging voltage to +13.8 V DC (at 20°C)
X 2 / 3
Basic module connector
Power supply modu