EasyManua.ls Logo

Fluke 54200 - Synchronization

Fluke 54200
386 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Remote Control
Remote Control Commands
6
6-19
Synchronization
*OPC Operating Complete Command
Sending a command using the IEEE-488 bus, followed by the command *OPC in the
same string, sets bit 0 (operation complete) of the 'Standard Event Status Register' to 1
when the function is finished. This bit activates bit 5 of the 'Status Byte Register' (Event
Status Bit), which generates a Service Request. This alerts the controller that the function
is finished. See Page 6-15 to enable the Service Request.
*OPC? Operation Complete Query
Sending the query *OPC? to the generator during a running function causes the
instrument to wait until the function is finished, and then set a 1 in the output queue. The
register can be read out by the controller without a Service Request. When a 1 is
returned, your user program can then continue.
Data in the output queue activate bit 4 of the 'Status Byte Register' (MAV, message
available), which may generate a Service Request. To avoid generating an SRQ, disable
bit 4 (set it to 0). Bit 0 (operation complete) of the 'Standard Event Status Register' is not
affected by *OPC?
Contrary to *OPC, the query *OPC? is more convenient for the RS-232 Interface
because the 1 is directly sent; a separate read-out is not necessary as it would be for the
IEEE-488 Interface.
If *OPC? is sent when the operation is already finished, bit 0 is not set to 1.
*WAI Wait-to-Continue Command
This command sent to the instrument in a message string with other commands causes
the generator to execute the command following *WAI only when the previous
command is completed.
Example:
FREQ 500M;*SAV 10;*WAI;FREQ 400M
The command *WAI in this string causes the instrument to change the frequency setting
to 400 MHz after the previous setting of 500 MHz has been stored.

Table of Contents