4 Electrical and control settings
Unit electrical wiring and connection
SMGB0099 rev.0 - 12/2016
133
4
4.1.2 Minimum requirements of the protection devices
! CAUTION
Ensure specically that there is an Earth Leakage Breaker (ELB) installed for the units.
If the installation is already equipped with an Earth Leakage Breaker (ELB), ensure that its rated current is large enough to hold the
current of the units.
? NOTE
Electric fuses can be used instead of magnetic Circuit Breakers (CB). In that case, select fuses with similar rated values as the CB.
The Earth Leakage Breaker (ELB) mentioned on this manual is also commonly known as Residual Current Device (RCD) or Residual
Current Circuit Breaker (RCCB).
The Circuit Breakers (CB) are also known as Thermal-Magnetic Circuit Breakers or just Magnetic Circuit Breakers (MCB).
Indoor units
Model Power supply Maximum current (A) CB (A)
ELB
(nº poles/A/mA)
Indoor units (0.6-6.0) HP
1~ 230V 50Hz
or
1~ 220-240V 50Hz
(depending on model)
5.0 6
2/40/30
RPI-(8.0/10.0)FSN3E(-f) 10.0 10
RPI-16.0FSN3PE(-f) 16.2 20
RPI-20.0FSN3PE(-f) 17.7 20
CB: Circuit breaker; ELB: Earth leakage breaker
KPI units
Model Power source Maximum current (A) CB (A)
ELB
(nº poles/A/mA)
KPI-252E4E
1~ 230V50Hz
4.0 6
2/40/30
KPI-502(E/X)4E 4.0 6
KPI-802(E/X)4E 4.0 6
KPI-1002(E/X)4E 8.0 10
KPI-1502E4E 8.0 16
KPI-2002E4E 8.0 16

Table of Contents

Other manuals for Hitachi P-N23NA2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi P-N23NA2 and is the answer not in the manual?

Hitachi P-N23NA2 Specifications

General IconGeneral
BrandHitachi
ModelP-N23NA2
CategoryAir Conditioner
LanguageEnglish

Related product manuals