2 Unit installation
Econofresh Kit
SMGB0099 rev.0 - 12/2016
74
2.11.4  Example of installation
1  Ducting Connection
Pre-drilled duct anges are provided at the supply, return and outdoor air intake connections. It is recommended that 
a exible duct connection be installed to minimize sound and vibration transmission.
2  Insulation
All ducts should be insulated
 - Especially the outdoor air duct, through which the cold outdoor air ows in, must be sufciently insulated.
 - The lowest temperature of the entering outdoor air owing through the outdoor air duct is the lowest temperature 
for heating operation at the installation site.
Supply Air Duct
RPI Unit
Econofresh
Outdoor Air Duct  
(Fully Insulated)  
(Field-Supplied)
Downward 
Gradient of Duct
Outdoor 
Thermistor 
(Accessory)
Rain Hood with 
Bird Screen 
(Field-Supplied)
Pressure relief damper (eld supplied), connected 
if necessary to the outside or to another place with 
atmospheric pressure)
Return Air Filter 
(Field-Supplied)
Return Air 
Duct
Thermistor Cable 
(Accessory)
AS Motor Cable 
(Accessory)
Refrigerant 
Piping
Insulate  
(Field-Supplied) 
5 mm
 
In the case that the unit is used under the following condition, perform additional insulation (*) or prepare a drain pan 
underneath the unit.
? NOTE
Ducting arrangement must comply with local regulations.
 
30ºC 
*20 mm 
*10 mm
*5 mm 
80%RH 
70%RH 
Saturation 
Curve 
Ambient Temperature around Unit
? NOTE
For further information regarding this product, refer to the installation and operation manual.