9.7.7 Removal of the oat switch
For RPI-(8.0/10.0)FSN3E(-f)
1 Remove all screws -A- from the lower cover of the unit and
separate it.
2 Remove the drain pan as indicated in chapter “9.7.5 Removal of
the drain pan”.
? NOTE
To disconnect and remove the oat switch, previously see the chapter
corresponding to the wiring diagrams in this Manual.
3 Loosen the resin nut securing the oat switch -A- and remove it. 
If the switch support is to be removed, remove screws -B-.
? NOTE
The torque value of the resin nut is 0.3 - 0.4 Nm. If the torque value is
higher, the nut will be damaged.
For RPI-(16.0/20.0)FSN3PE(-f)
1 Remove the cycle service cover by unscrewing its xing screws
2 Loosen the resin nut securing the oat switch and remove it. If 
the switch support is to be removed, remove screws.
? NOTE
The torque value of the resin nut is 0.3 - 0.4 Nm. If the torque value is
higher, the nut will be damaged.
Cycle
service
cover
Flow switch

Table of Contents

Other manuals for Hitachi P-N23NA2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi P-N23NA2 and is the answer not in the manual?

Hitachi P-N23NA2 Specifications

General IconGeneral
BrandHitachi
ModelP-N23NA2
CategoryAir Conditioner
LanguageEnglish

Related product manuals