6 Optional functions
Optional functions through Remote control
SMGB0099 rev.0 - 12/2016
212
Elem. Optional function
Individual
setting
Settings Setting conditions Description
d4
Cooling air temperature
drop prevention.
Models,
RPI-FSN3(P)E
RPC-FSN3E
RPF(I)-FSN2E
RCI-FSN4
RPC-FSN3
RPK-FSN3M
RPI-FSN4E
RPIM-FSN4E(-DU)
O
00 Not activated function
This function changes the cooling
operating conditions to avoid cold
draughts.
Not available for models
RCD-FSN3
RCIM-FSN4(E)
(Use as 00 conditions)
01 Activated function
d5
Prevention of decrease
of heating discharge air
temperature
O
00 Not activated function
This function prevents a drop in the
air temperature by decreasing the fan
speed, apart from the settings on the
remote control.
01 Activated function
d6
Room temperature
control for energy saving
O
00 Not activated function
This function saves energy when the
outdoor temperature is lower than the
air conditioning charge.
Function of the outdoor unit
Not available for models
RCD-FSN3
RCIM-FSN4(E)
(Use as 00 conditions)
01 Activated function
d7
Econofresh: OA Damper
minimum opening
O
00 6º
This function is used to set the fresh
outdoor air damper minimum opening
selection.
01 12º
02 18º
03 24º
04 30º
05 36º
06 42º
07 48º
E1
Econofresh cooling mode O
00 Standard Process
This function allows to the outdoor
air damper to be opened in All Fresh
Operation mode. This mode able to
fully open the outdoor air damper
(according to the control system)
01/02 All-fresh
E2
Econofresh enthalpy
sensor
O
00 Not activated function
This function selects the enthalpy
sensor input.
01 Activated function
E3 Not available O
00
Not available
Use at 00 conditions
–
01
E4 Econofresh: CO2 sensor O
00 Standard
This function selects the CO2 gas
sensor input.
01/02 CO2 sensor
E5 Not available O
00
Not available
Use at 00 conditions
–
01
E6
Indoor fan operation time
after cooling operation
stoppage
O
00 Not activated function This function prevents the
condensation accumulation in the unit
by keeping the fan running after it is
switched off.
01 60 minutes
02 120 minutes
E7 Not available O
00
Not available
Use at 00 conditions
–
01
E8
Fan operation control at
heating Thermo - OFF
O
00 Not activated function
This function reduces the unit fan
speed to prevent cold draughts.
01 Activated function
E9 Not available O
00
Not available
Use at 00 conditions
–
01

Table of Contents

Other manuals for Hitachi P-N23NA2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi P-N23NA2 and is the answer not in the manual?

Hitachi P-N23NA2 Specifications

General IconGeneral
BrandHitachi
ModelP-N23NA2
CategoryAir Conditioner
LanguageEnglish

Related product manuals