Automatic restart (retry) related parameters.
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
B001
Restart mode on power
failure / under-voltage trip
Select inverter restart method,
Five option codes:
00…Alarm output after trip, no
automatic restart
01…Restart at 0Hz
02…Resume operation after
frequency matching
03…Resume previous freq.
after freq. matching, then
decelerate to stop and
display trip info
04…Resume operation after
active freq. matching
U
00
−
B002
Allowable under-voltage
power failure time
The amount of time a power
input under-voltage can occur
without tripping the power
failure alarm. Range is 0.3 to
25 sec. If under-voltage exists
longer than this time, the
inverter trips, even if the
restart mode is selected.
U
1.0 sec.
B003
Retry wait time before motor
restart
Time delay after under-voltage
condition goes away, before the
inverter runs motor again.
Range is 0.3 to 100 seconds.
U
1.0 sec.
B004
Instantaneous power failure
/ under-voltage trip alarm
enable
Three option codes:
00…Disable
01…Enable
02…Disable during stop and
decelerates to a stop
U
00
−
B005
Number of restarts on power
failure / under-voltage trip
events
Two option codes:
00…Restart 16 times
01…Always restart
U
00
−
b007
Restart frequency threshold Restart the motor from 0Hz if
the frequency becomes less
than this set value during the
motor is coasting, range is 0 to
400Hz
U
0.00 Hz