346
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
b008
Restart mode on over voltage
/ over current trip
Select inverter restart method,
Five option codes:
00Alarm output after trip, no
automatic restart
01Restart at 0Hz
02Resume
operation after
frequency
matching
03Resume previous freq.
after active freq. matching,
then decelerate to stop and
display trip info
04Resume operation after
active freq. matching
U
00
b010
Number of retry on over
voltage / over current trip
Range is 1 to 3 times
U
3
times
b011
Retry wait time on over
voltage / over current trip
Range is 0.3 to 100 sec.
U
1.0 sec