specify data displayed on the integrated operator on powerup. The table below lists the
display items selectable. (The factory setting is 01 [d001].)
Panel display selection: B150 – When an external operator is connected to WJ200 via
RS-422 port, the display is locked and shows only one parameter configured by B150.
Automatic return to the initial display: b164 10 min. after the last key operation,
display returns to the initial parameter set by b038.
Frequency conversion coefficient setting: b086 By setting b086, converted output
frequency is monitored in d007. (d007 = d001 × b086)
Frequency set in monitoring: b163 If 01 is set in b163, frequency can be changed by
up/down key in monitor display d001 and d007.
Action selection in case of external operator disconnection: b165 When an external
operator is disconnected, the inverter behaves according to b165 setting.