3−60
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
b038
Initial display selection
000…Func. code that SET key
pressed last displayed.(*)
001~030…d001~d030 displayed
201…F001 displayed
202…B display of LCD operator
U
001
−
B086
Frequency scaling
conversion factor
Specify a constant to scale the
displayed frequency for D007
monitor, range is 0.01 to 99.99
U
1.00
−
b150
Display ex.operator
connected
When an external operator is
connected via RS-422 port, the
built-in display is locked and
shows only one "d" parameter
configured in:
d001 ~ d030
U
001
−
b160
1st parameter of Dual
Monitor
Set any two "d" parameters in
b160 and b161, then they can be
monitored in d050. The two
parameters are switched by
up/down keys.
Set range: d001 ~ d030
U
001
−
b161
2nd parameter of Dual
Monitor
U
002
−
b163
Frequency set in monitoring Two option codes:
00…Freq. set disabled
01…Freq. set enabled
00
−
b164
Automatic return to the
initial display
10 min. after the last key
operation, display returns to the
initial parameter set by b038.
Two option codes:
00…Disable
01…Enable
00
−
b165
Ex. operator com. loss action Five option codes:
00…Trip
01…Trip after deceleration to a
stop
02…Ignore
03…Coasting (FRS)
04…Decelerates to a stop
02
−
(*) note: If the power is off with displaying “000” after the set, b038 comes when power is on
again.