B43
2(EzCOM<administrator>)
1465h (Reserved) - - - -
1466h EzCOM start adr. of master C098 R/W 18
1467h EzCOM end adr. of master C099 R/W 18
1468h EzCOM starting trigger C100 R/W 00(Input terminal), 01(Always)
1469h Up/Down memory mode selection C101 R/W
0 (not storing the frequency data), 1
(storing the frequency data)
-
146Ah Reset mode selection C102 R/W
0 (resetting the trip when RS is on), 1
(resetting the trip when RS is off), 2
(enabling resetting only upon tripping
[resetting when RS is on]), 3(resetting
only trip)
-
146Bh Restart mode after reset C103 R/W
0 (starting with 0 Hz), 1 (starting with
matching frequency), 2 (restarting with
active matching frequency)
-
146Ch
UP/DWN clear mode
C104 R/W
0 (0Hz)/1 (EEPROM data)
-
146Dh FM gain adjustment C105 R/W 50 to 200 1 [%]
146Eh AM gain adjustment C106 R/W 50 to 200 1 [%]
146Fh
(Reserved) - - Inaccessible
1 [%]
1471h AM bias adjustment C109 R/W 0 to 100 1 [%]
1472h (Reserved) - - - 1 [%]
1473h Overload warning level 2 C111 R/W 0 to 2000 0.1 [%]
1474h to
1485h
(Reserved) - - - -
1486h Output [11] on-delay time C130 R/W 0 to 1000 0.1 [sec.]
1487h Output [11] off-delay time C131 R/W 0 to 1000 0.1 [sec.]
1488h Output [12] on-delay time C132 R/W 0 to 1000 0.1 [sec.]
1489h Output [12] off-delay time C133 R/W 0 to 1000 0.1 [sec.]
148Ah to
148F
(Reserved) - - - -
1490h Output RY on-delay time C140 R/W 0 to 1000 0.1 [sec.]
1491h Output RY off-delay time C141 R/W 0 to 1000 0.1 [sec.]
1492h Logic output 1 operand A C142 R/W
Same as the settings of C021 to C026
(except those of LOG1 to LOG6, OPO,
no)
-
1493h Logic output 1 operand B C143 R/W
Same as the settings of C021 to C026
(except those of LOG1 to LOG6, OPO,
no)
-
1494h Logical output 1 operato
r
C144 R/W 0 (AND), 1 (OR), 2 (XOR) -
1495h Logic output 2 operand A C145 R/W
Same as the settings of C021 to C026
(except those of LOG1 to LOG6, OPO,
no)
-
1496h Logic output 2 operand B C146 R/W
Same as the settings of C021 to C026
(except those of LOG1 to LOG6, OPO,
no)
-
1497h Logical output 2 operato
r
C147 R/W 0 (AND), 1 (OR), 2 (XOR) -
1498h Logic output 3 operand A C148 R/W
Same as the settings of C021 to C026
(except those of LOG1 to LOG6, OPO,
no)
-
1499h Logic output 3 operand B C149 R/W
Same as the settings of C021 to C026
(except those of LOG1 to LOG6, OPO,
no)
-
149Ah Logical output 3 operato
r
C150 R/W 0 (AND), 1 (OR), 2 (XOR) -
149Bh to
14A3h
(Reserved) - - -
-
14A4h Input [1] response time C160 R/W 0 to 200
14A5h Input [2] response time C161 R/W 0 to 200
14A6h Input [3] response time C162 R/W 0 to 200
14A7h Input [4] response time C163 R/W 0 to 200
14A8h Input [5] response time C164 R/W 0 to 200
14A9h Input [6] response time C165 R/W 0 to 200
14AAh Input [7] response time C166 R/W 0 to 200
14ABh to
14ACh
(Reserved) - - -
14ADh Multistage speed/position determination time C169 R/W 0 to 200
14A4h to
1500h
unused - - Inaccessible -