B−42
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
142Ah
Frequency arrival setting for accel.
C042 (high) R/W
0 to 40000 0.01 [Hz]
142Bh C042 (low) R/W
142Ch
Frequency arrival setting for decel.
C043 (high) R/W
0 to 40000 0.01 [Hz]
142Dh C043 (low) R/W
142Eh PID deviation level C044 R/W 0 to 1000 0.1 [%]
142Fh
Frequency arrival setting 2 for
accel.
C045 (high) R/W
0 to 40000 0.01 [Hz]
1430h C045 (low) R/W
1431h
Frequency arrival setting 2 for
decel.
C046 (high) R/W
0 to 40000 0.01 [Hz]
1432h C046 (low) R/W
1433h
Pulse train input scale conversion
for EO output
C047 R/W 0.01 – 99.99
-
1434h to
1437h
(Reserved) - - - -
1438h Maximum PID feedback data C052 R/W 0 to 1000 0.1 [%]
1439h Minimum PID feedback data C053 R/W 0 to 1000 0.1 [%]
143Ah
Over-torque/under-torqueselection
C054 R/W 0(Over torque)/1(under torque)
-
143Bh
Over-torque (forward-driving) level
setting
C055 R/W 0 to 200 1 [%]
143Ch
Over-torque (reverse
regenerating) level setting
C056 R/W 0 to 200 1 [%]
143Dh
Over-torque (reverse driving) level
setting
C057 R/W 0 to 200 1 [%]
143Eh
Over-torque (forward
regenerating) level setting
C058 R/W 0 to 200 1 [%]
143Fh
Signal output mode of Over/under
torque
C059 R/W
00 (output during
acceleration/deceleration and
constant-speed operation), 01 (output
only during constant-speed operation)
-
1440h (Reserved) - - - -
1441h Electronic thermal warning level C061 R/W 0 to 100 1 [%]
1442h
(Reserved) - - -
1443h Zero speed detection level C063 R/W 0 to 10000 0.01 [Hz]
1444h Heat sink overheat warning level C064 R/W 0 to 110 1 [℃]
1445h to
144Ah
(Reserved) - - - -
144Bh Communication speed C071 R/W
03(2400bps), 04(4800bps),
05(9600bps) 06(19.2kbps),
07(38.4kbps),,08(57.6kbps),
09(76.8kbps), 10(115.2kbps)
-
144Ch Modbus address C072 R/W 1. to 247. -
144Dh (Reserved) - - - -
144Eh Communication parity C074 R/W
00 (no parity), 01 (even parity), 02 (odd
parity)
-
144Fh Communication stop bit C075 R/W 1 (1 bit), 2 (2 bits) -
1450h
Selection of the operation after
communication error
C076 R/W
0 (tripping), 1 (tripping after decelerating
and stopping the motor), 2 (ignoring
errors), 3 (stopping the motor after
free-running), 4 (decelerating and
stopping the motor)
-
1451h Communication timeout limit C077 R/W 0 to 9999 0.01 [sec.]
1452h Communication wait time C078 R/W 0 to 1000 1 [msec.]
1453h to
1454h
(Reserved) - - - -
1455h [O] input span calibration C081 R/W 0 to 2000 0.1
1456h [OI] input span calibration C082 R/W 0 to 2000 0.1
1457h to
1458h
(Reserved) - - - -
1459h Thermistor input tuning C085 R/W 0 to 2000 0.1
145Ah to
145Eh
(Reserved) - - - -
145Fh Debug mode enable C091 R 0/1 -
1460h to
1463h
(Reserved) - - - -
1464h Communication selection C096 R/W 0(Modbus-RTU) 1(EzCOM)